OPERATIONAL LIMITATIONS (ENGLISH)
TABLE 2 – TEMPERATURES AND FLOWS
LEAVING WATER
TEMPERATURE (°F)
YCAL
MIN
0041
40
0045
40
0051
40
0055
40
0061
40
0065
40
0071
40
Voltage Limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
TABLE 3 – VOLTAGE LIMITATIONS
UNIT POWER
MIN.
380-415/3/50
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Johnson Controls Office for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest Johnson Controls Office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
4. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system.
5. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
JOHNSON CONTROLS
SECTION 6 - TECHNICAL DATA
MAX
55
55
55
55
55
55
55
MAX.
355
415
ENGLISH
COOLER FLOW (GPM)
MIN
MAX
40
200
40
200
40
200
60
300
60
300
60
300
60
300
Excessive flow will cause damage to
the cooler. Do not exceed max. cooler
flow. Special care should be taken
when multiple chillers are fed by a
single pump.
AIR ON CONDENSER (°F)
MIN
MAX
0
125
0
125
0
125
0
125
0
125
0
125
0
125
45
6