Program Key - York YCAL Series Installation Operation & Maintenance

Air-cooled scroll chillers style d with ipu ii and i/o boards (50 hz) 29 ton to 65 ton
Hide thumbs Also See for YCAL Series:
Table of Contents

Advertisement

FORM 150.66-NM3
ISSUE DATE: 09/25/2020

Program Key

There are several operating parameters under the PRO-
GRAM key that are programmable. These setpoints
can be changed by pressing the PROGRAM key, and
then the ENTER/ADV key to enter Program Mode.
Continuing to press the ENTER/ADV key will display
each operating parameter. While a particular parameter
is being displayed, the ↑ (UP) and ↓ (DOWN) arrow
keys can be used to change the value. After the value
is changed, the ENTER/ADV key must be pressed to
enter the data into memory. Table 16 shows the pro-
grammable limits and default values for each operating
parameter.
Following are the displays for the programmable val-
ues in the order they appear:
D I S C H A R G E
d
C U T O U T
=
DISCHARGE PRESSURE CUTOUT is the discharge
pressure at which the system will shutdown as moni-
tored by the optional discharge transducer. This is a
software shutdown that acts as a backup for the me-
chanical high pressure switch located in the refrigerant
circuit. The system can restart when the discharge pres-
sure drops 75 psig (5.17 barg) below the cutout point.
If the optional discharge pressure transducer is not in-
stalled, this programmable safety would not apply. It
should be noted that every system has a mechanical
high pressure cutout that protects against excessive
high discharge pressure regardless of whether or not
the optional discharge pressure is installed.
S U C T I O N
C U T O U T
=
The SUCTION PRESSURE CUTOUT protects the
chiller from an evaporator freeze-up. If the suction
pressure drops below the cutout point, the system
will shut down. Typically, the cutout should be set to
80 psig (5.5 bar) form water cooling.
There are some exceptions when the
suction pressure is permitted to tem-
porarily drop below the cutout point.
Details are explained under the topic
of SYSTEM SAFETIES.
JOHNSON CONTROLS
P R E S S U R E
6 3 7
P S I G
P R E S S U R E
8 0
P S I G
L O W
A M B I E N T
C U T O U T
The LOW AMBIENT TEMP CUTOUT allows the user
to select the chiller outside ambient temperature cutout
point. If the ambient falls below this point, the chiller
will shut down. Restart can occur when temperature
rises 2°F (1.11°C) above the cutout setpoint.
L E A V I N G
L I Q U I D
C U T O U T
=
The LEAVING LIQUID TEMP CUTOUT protects
the chiller from an evaporator freeze-up. Anytime the
leaving chilled liquid temperature drops to the cutout
point, the chiller shuts down. Restart will be permitted
when the leaving chilled liquid temperature rises 2°F
(1.11°C) above the cutout setpoint.
When water cooling mode is programmed (Options
key), the value is fixed at 36.0°F (2.22°C) and cannot
be changed. Glycol cooling mode can be programmed
to values listed in table 15.
A N T I
R E C Y C L E
=
6 0 0
The programmable anti-recycle timer ensures that sys-
tems do not short cycle, and the compressor motors have
sufficient time to dissipate heat after a start. This timer
is programmable under the PROGRAM key between
300 and 600 seconds. Whenever possible, to reduce cy-
cling and motor heating, the anti-recycle timer should
be adjusted as high as possible. The programmable anti-
recycle timer starts the timer when the first compressor
in a system starts. The timer begins to count down. If all
the compressors in the circuit cycle off, a compressor
within the circuit will not be permitted to start until the
anti-recycle timer has timed out. If the lead system has
run for less than 5 minutes, 3 times in a row, the anti-
recycle timer will be extended to 10 minutes, if currently
programmed for less than 10 minutes.
F A N
C O N T R O L
P R E S S U R E
The Fan Control On-Pressure is the programmed pressure
value that is used to stage the condenser fans on, in rela-
tion to discharge pressure. See Condenser Fan Control
(YCAL0041 – YCAL0071 Chillers) and Tables 22, 23,
and 24.
SECTION 7 - UNIT CONTROLS
T E M P
=
2 5 . 0 ° F
T E M P
3 6 . 0 ° F
T I M E R
S E C
O N
=
X X X
P S I G
119
7