Wiring; Fig. 16 - Inverter Power Wiring Schematic; Fig. 17 - Inverter Wiring - York YCAL Series Installation Operation & Maintenance

Air-cooled scroll chillers style d with ipu ii and i/o boards (50 hz) 29 ton to 65 ton
Hide thumbs Also See for YCAL Series:
Table of Contents

Advertisement

FORM 150.66-NM3
ISSUE DATE: 09/25/2020

Wiring

VFD wiring is simple and requires only 3-phase power
in, 3-phase power out, and a 2-wire signal from the
transducer. No start, stop, or other alternate power re-
quirements are needed to run the VFD. Fig's 16 and 17
show the power and control wiring schematically as
well as the actual connections. The VFD controlled fan
will operate whenever the liquid line solenoid on the
respective system is energized.
7M
10M
FIG. 16 – INVERTER POWER WIRING SCHEMATIC
SYS 1
SYS 2
FIG. 17 – INVERTER WIRING
JOHNSON CONTROLS
150A
L1
T1
151A
L2
T2
SPEED
CONTR.
152A
L3
T3
250A
L1
T1
251A
L2
T2
SPEED
CONTR.
252A
L3
T3
TB3
TB1
TB1
TB1
TB3
TB3
BLK
BLK
152A
152A
WHT
WHT
(J7)
TO MICROBOARD (P4)
TO MICROBOARD (P4)
TO PANEL 7 M
TO PANEL 7 M
TB3
TB1
TB1
TB3
BLK
BLK
252A
252A
WHT
WHT
(J9)
TO MICROBOARD (P7)
TO MICROBOARD (P7)
TO PANEL 10 M
TO PANEL 10 M
On chillers with the low ambient op-
tion, wire 127 is removed from TB7­9
and connected to to TB7­3. Wire 227 is
removed from TB10­9 and connected
to TB10­3.
150
151
152
250
251
CONDENSER
252
151A
151A
150A
150A
150
150
TO FAN #1 (EXIS TING HARNESS)
TO FAN #1 (EXIS TING HARNESS)
251A
251A
250A
250A
250
250
TO FAN #2 (EXIS TING HARNESS)
TO FAN #2 (EXIS TING HARNESS)
NOTE: Fans must run in the forward direction (AIR ↑)
SECTION 8 - UNIT OPERATION
CONDENSER
FAN NO. 1
FAN NO. 2
LD11301
TB2
TB2
TB2
151
151
152
152
TB2
TB2
251
251
252
252
8
LD11302
139