Table 1 - Setpoints Entry List - York YCAL Series Installation Operation & Maintenance

Air-cooled scroll chillers style d with ipu ii and i/o boards (50 hz) 29 ton to 65 ton
Hide thumbs Also See for YCAL Series:
Table of Contents

Advertisement

SECTION 5 - COMMISSIONING
TABLE 1 – SETPOINTS ENTRY LIST
OPTIONS
Display Language
Sys 1 Switch
Sys 2 Switch
Chilled Liquid
* Ambient Control
Local/Remote Mode
Control Mode
Display Units
* Lead/Lag Control
* Fan Control
Manual Override
Current Feedback
** Soft Start
** Unit Type
** Refrigerant Type
** Expansion Valve Type
COOLING SETPOINTS
Cooling Setpoint
Range
EMS-PWM Max. Setpoint
PROGRAM
Discharge Pressure Cutout
Suct. Pressure Cutout
Low Amb. Temp. Cutout
Leaving Liquid Temp. Cutout
Anti-Recycle Time
Fan Control On Pressure
Fan Differential Off Pressure
Total # of Compressors
* Number of Fans/System
* Unit/Sys Voltage
Unit ID
* Sys 1 Superheat Setpoint
* Sys 2 Superheat Setpoint
* NOT ON ALL MODELS
** VIEWABLE ONLY
 5. Before this step, turn system 2 off (if applicable
–refer to Option 2 under "Unit Keys" section for
more information on system switches). Connect a
manifold gauge to system 1 suction and discharge
service valves.
Place the Unit Switch in the control panel to the
"ON" position. As each compressor cycles on,
ensure that the discharge pressure rises and the
suction pressure decreases. If this does not oc-
42
cur, the compressor being tested is operating in
the reverse direction and must be corrected. After
verifying proper compressor rotation, turn the
Unit Switch to "OFF."
The chilled liquid setpoint may need
to be temporarily lowered to ensure all
compressors cycle "on."
This unit uses scroll compressors
which can only operate in one direc-
tion. Failure to observe this will lead
to compressor failure.
 6. YCAL0041 - YCAL0071 units only – Turn system
1 "OFF" and system 2 "ON" (refer to Option 2
under Unit Keys for more information on system
switches).
Place the Unit Switch in the control panel to the
"ON" position. As each compressor cycles "ON",
ensure that the discharge pressure rises and the
suction pressure decreases. If this does not oc-
cur, the compressor being tested is operating in
the reverse direction and must be corrected. After
verifying proper compressor rotation, turn the
Unit Switch to "OFF".
The chilled liquid setpoint may need
to be temporarily lowered to ensure all
compressors cycle "ON".
FORM 150.66-NM3
ISSUE DATE: 09/25/2020
JOHNSON CONTROLS

Advertisement

Table of Contents
loading

Table of Contents