York YCAL Series Installation Operation & Maintenance page 121

Air-cooled scroll chillers style d with ipu ii and i/o boards (50 hz) 29 ton to 65 ton
Hide thumbs Also See for YCAL Series:
Table of Contents

Advertisement

FORM 150.66-NM3
ISSUE DATE: 09/25/2020
Unit Trip Volts
For total chiller high current trip programming on
460VAC chillers:
• Add the sum of all the the compressor and fan RLA's
in the chiller.
• Multiply the sum by 1.25
• Divide by 225 A
• The resulting voltage is the value that should be
programmed.
For example, if fan and compressor RLA's total 180A:
5 V x 180 A
x
1.25 =
225 A
The programmed value will be 5.0V.
R E M O T E
U N I T
P R O G R A M M E D
When communications is required with a BAS or Op-
tiView Panel, individual unit IDs are necessary for
communications with specific chillers on a single RS-
485 line. ID 0-7 is selectable.
JOHNSON CONTROLS
1125 VA
= 5.0 V
225 A
I D
=
X
S Y S
1
S U C T
S E T P O I N T
S Y S
2
S U C T
S E T P O I N T
These messages only appear and are programmable
when EEV is selected as the expansion valve type in
the Service Mode. EEV must only be selected when an
EEV is installed. Superheat is programmable between
10°F and 15°F. A setpoint of 12°F to 15°F is recom-
mended.
SECTION 7 - UNIT CONTROLS
S U P E R H E A T
=
X X . X ° F
S U P E R H E A T
=
X X . X ° F
121
7