SECTION 7 - UNIT CONTROLS
Option 9 – Condenser Fan Control Mode
F A N
C O N T R O L
D I S C H A R G E
Condenser fans are controlled by discharge pressure
only. This mode may only be chosen when discharge
pressure transducers are installed.
F A N
C O N T R O L
A M B I E N T
&
Condenser fans are controlled by ambient temperature
and discharge pressure. This mode must be chosen if
the discharge pressure transducers are not installed.
Option 10 – Manual Override Mode
M A N U A L
O V E R R I D E
D I S A B L E D
This option allows overriding of the daily schedule that
is programmed. MANUAL OVERRIDE MODE – DIS-
ABLED indicates that override mode has no effect.
M A N U A L
O V E R R I D E
E N A B L E D
Manual Override Mode is enabled. This is a service
function and when enabled, will allow the unit to start
when shut down on the daily schedule. It will auto-
matically be disabled after 30 minutes.
Option 11 – Current Feedback Options In-
stalled
C U R R E N T
N O N E
This mode should be selected when the panel is not
equipped with current sensing capability.
C U R R E N T
O N E
P E R
This mode should be selected when an optional 2ACE
Module is installed to allow combined current moni-
toring of all systems by sensing current on the incom-
ing line. Current input is to J7 of the I/O board.
126
P R E S S U R E
or
D S C H
P R E S S
M O D E
or
M O D E
F E E D B A C K
or
F E E D B A C K
U N I T
C U R R E N T
O N E
P E R
This mode should be selected when an optional 2ACE
module is installed to allow individual current moni-
toring of each system. SYS 1 input is to J7 of the I/O
board SYS 2 input is to J9 of the I/O board.
Option 12 – Power Fail Restart
P O W E R
F A I L
A U T O M A T I C
Chiller auto restarts after a power failure.
P O W E R
F A I L
M A N U A L
After a power failure, the UNIT switch must be tog-
gled before restart at the unit is allowed. NORMALLY
MANUAL RESTART should NOT BE SELECTED.
Option 13 – Soft Start Enable/Disable
S O F T
D I S A B L E D
SOFT START "DISABLED" MUST be selected on
all chillers.
This message may not be viewable on non-Europe-
an chillers.
Option 14 – Unit Type
U N I T
L I Q U I D
The UNIT TYPE message cannot be modified under
the unit keys.
"LIQUID CHILLER" must be dis-
played, or damage to compressors
or other co mponents will occur if
operated in the HEAT PUMP or CON-
DENSING UNIT modes.
FORM 150.66-NM3
ISSUE DATE: 09/25/2020
or
F E E D B A C K
S Y S T E M
R E S T A R T
R E S T A R T
S T A R T
T Y P E
C H I L L E R