York YCAL Series Installation Operation & Maintenance page 66

Air-cooled scroll chillers style d with ipu ii and i/o boards (50 hz) 29 ton to 65 ton
Hide thumbs Also See for YCAL Series:
Table of Contents

Advertisement

SECTION 6 - TECHNICAL DATA
3 15/16"
47 3/4"
46 15/16"
ALUMINUM
CENTER OF GRAVITY (IN.)
YCAL
X
0045
59.2
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 6';
rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'. No
more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by 6".
66
DIMENSIONS - YCAL0045 (ENGLISH)
6 3/4"
3 1/4"
VIEW B-B
BOTTOM OF PANEL
LIQUID OUT
90 1/4" BASE WIDTH
LEFT END
Y
43.5
7/8" TYP.
LIQUID IN
3" VICTAULIC (typ)
45 1/8"
YCAL
0045
FORM 150.66-NM3
ISSUE DATE: 09/25/2020
ELECTRICAL ACCESS
PANEL
34 5/8"
9 15/16"
15 3/4"
12 5/8"
COPPER
CENTER OF GRAVITY (IN.)
X
63.2
43.7
JOHNSON CONTROLS
Y
LD10963

Advertisement

Table of Contents
loading

Table of Contents