Individual Control Functions; Notes - Siemens CS1140 Commissioning

Fire detection system. commissioning 'en12094-1 compliant single-area extinguishing system'
Hide thumbs Also See for CS1140:
Table of Contents

Advertisement

Performance checks
7.2

Individual control functions

Control functions
1
Check evacuation time
2
Check alarm horn switch-off function
3
Check illuminated warning panel switch-
off function
4
Check the duty cycle of main-/and sector
valve
5
Check line monitoring
6
Check ZONE affiliation
7
Check 'Blocking' function via AlgoPilot
'CT11' / list of functions 'SECTION'
8
Check 'Blocking' function via operating
unit extinguishing / keys
7.3

Notes

18
Building Technologies
Fire Safety
Comment
Dependent on parameterization
must correspond to the parameterized tim
Dependent on parameterization
may only be possible either from the operating unit extinguishing 'B3Q440' or the
operating unit extinguishing 'B3Q440' and AlgoPilot 'CT11'
Switch-off must always be possible except during the 'Evacuation'
Check whether alarm horn cannot be switched off during 'Evacuation'
Dependent on parameterization
either active until 'Reset'
or active until switched off separately via the operating unit extinguishing 'B3Q440'
Dependent on parameterization
either active until 'Reset'
or active during the time specified
Induce a short circuit or open line for all peripheral equipment in quiescent state
connected and check whether in each case a fault results
With 'valve lines' it is essential to induce open line and short circuit
In each detector ZONE belonging to the extinguishing SECTION activate 1 detector
and check whether the extinguishing horn is activated
Dependent on parameterization
In each detector ZONE belonging to the extinguishing SECTION, activate 2 (or 3)
detectors and check whether the 'Evacuation' phase is initiated
choose list of functions 'SECTION' and check following functions:
Manual activation of extinguishing BLOCKING / ENABLE
Automatic activation of extinguishing BLOCKING / ENABLE
Extinguishing -> REVISION / terminate
Extinguishing -> TEST / terminate
Here the corresponding LEDs
AlgoPilot 'CT11' must always on
Check at the extinguishing control panel whether by means of both keys
,
activation at extinguishing can be blocked accordingly
Here the corresponding LEDs
AlgoPilot 'CT11' must always on
Use of valve actuators
Ensure that the minimum trigger current (comply with manufacturers' instructions)
can also be achieved without difficulty even with emergency power operation
(operating voltage 23.5V). Balance the difference between the 'internal resistance
valve actuators' (e.g. 1.5 ) and the 'minimum line impedance' (16 ) with series
resistor.
,
at the operating unit extinguishing 'B3Q440' and
,
at the operating unit extinguishing 'B3Q440' and
,
009853_b_en_--
01.2013