Installation - Emerson Rosemount 2460 Quick Start Manual

System hub
Hide thumbs Also See for Rosemount 2460:

Advertisement

Quick Start Guide
4

Installation

4.1
Installation considerations
The Rosemount 2460 System Hub may be installed on various non-
hazardous locations at the plant.
In case the system hub is exposed to long periods of sunshine, a
sunshade should be used to prevent the system hub from being heated
to temperatures above the maximum operating temperature. Sunshade
is to be manufactured and designed locally to suit the installation.
Ensure that environmental conditions are within specified limits.
Ensure that the system hub is installed such that it is not exposed to
higher pressure and temperature than specified.
Do not install the system hub in non-intended applications, for example
environments where it may be exposed to extremely intense magnetic
fields or extreme weather conditions.
Use an external circuit breaker in order to make sure that power supply
can be safely disconnected when wiring and servicing the system hub.
The circuit breaker shall be easily accessible and appropriately labeled.
In case devices from other vendors will be connected to the system hub,
ensure that correct modem cards are installed for the field ports that will
be used.
Ensure that correct firmware version is used that supports the desired
communication options and features.
Ensure that TankMaster version 6.B6 or higher is used for Rosemount
2460 configuration.
TankMaster 6.C0 and higher is required for configuration of Enraf
communication on field ports.
TankMaster 6.D0 and higher is required for configuration of redundant
system hubs.
Important
Check the system hub for any signs of damage prior to installation.
Ensure that O-rings and gaskets are in good condition.
Check that all modems are firmly mounted in their slots and cannot move.
Related information
Rosemount 2460 reference manual
12
September 2020
Rosemount 2460 Tank Hub