Quick Start Guide
Redundancy setup via Web graphical user interface
This section describes how to use the the Web graphical interface for
redundancy setup of a Rosemount 2460 System Hub. The setup includes
two basic steps:
Paring; two system hubs are setup as a redundant pair
Redundancy configuration; addresses and fail-over criteria are
configured
Pairing
Prerequisites
For the system hubs to be able to pair, ensure that the preconditions are
fulfilled.
Procedure
1. Log in to the Web interface.
2. Select the Redundancy tab.
3. Expand the Pair option.
4. Verify that the other system hub is pairable, i.e. all requirements for
pairing are marked with a green button.
5. If the two system hubs (Primary and Backup) are ready for pairing,
click the Pair button to start the synchronization process.