Eaton i-on Series Engineering Manual page 74

Next generation
Hide thumbs Also See for i-on Series:
Table of Contents

Advertisement

Technical Alarm (06)
Active when there is a technical alarm. Deactivates when the zone causing the alarm
is restored AND a user enters a valid access code to acknowledge the technical
alarm alert.
Confirmed Alarm (07)
Active when there is a confirmed alarm. Deactivates when the system is reset. The
operation of this output type depends on the option selected in System Options –
Confirmation – Confirmation Mode (see page 86):
RF Low Battery (08)
Active when a wirefree detector reports a low battery. The output remains active until
all detectors stop reporting low batteries.
RF Supervision (09)
Active when there is a supervision failure on any radio zone. The output remains
active until all supervision failures are reset.
RF Jamming (10)
Active when the control unit detects jamming. The output remains on until all
jamming disappears and the system is reset.
RF Fault (11)
Active when there are any of the following faults: RF Low Battery, RF supervision, RF
jamming and the system is reset.
A/C Fail (12)
Active when either mains power is absent, or a zone of type External PSU A/C Fail
has been triggered. The action of this output depends on the value programmed in
System Options – Mains Fail Delay (see page 98).
Battery Fault (13)
Active when the control unit detects a fault with its backup battery, or a zone of type
External PSU Battery Fault has been triggered. If the alert was caused by an
External PSU Battery Fault zone, the control unit deactivates the output when the
zone has been restored and a user has acknowledges the fault by entering a valid
access code.
If the alert was caused by a fault with the control unit's backup battery, the control
unit deactivates the output when it detects a good battery.
Ext PSU Low Volts (14)
Active when an external power supply has triggered an External PSU Low Volts
zone.
The control unit deactivates the output when the zone has been restored and a user
has acknowledges the fault by entering a valid access code.
Ext PSU Fault (15)
Active when an external power supply triggers a zone of type External PSU Fault.
The control unit deactivates the output when the zone has been restored and a user
has acknowledges the fault by entering a valid access code.
Tamper (16)
Active when the control unit detects a tamper at the control unit (lid or back), or at a
wired keypad, radio keypad, detector, expander, sounder, or when there is an
activation of a zone of type Tamper.
The control unit deactivates the output when tamper is reset.
Outputs Menu
Page 64

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-on30rI-on40h

Table of Contents