Parameter assignment
9.4 Assigning parameters using remote operation
3.55 mA
Upper fault current parameter
Adjusts the magnitude of the upper fault current
Setting range:
Factory setting:
3.55 mA
See also
Setting the fault current of the internal transmitter with switch to ≥ 21 mA (Page 175)
9.4.9.2

Lower saturation limit parameter

Sets the lower threshold for the lower saturation limit
168
3.8 mA
4 mA
Normal operation
Lower fault current (factory setting)
Lower saturation limit (factory setting)
Upper saturation limit (factory setting)
Upper fault current (factory setting)
Between upper saturation limit
22.8 mA, or as specified in order
3.8 mA
4 mA
Normal operation
Lower fault current (factory setting)
Lower saturation limit (factory setting)
Upper saturation limit (factory setting)
Upper fault current (factory setting)
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
20.5 mA
20 mA
.
und 22.8 mA
20.5 mA
20 mA
.
Operating Instructions, 05/2020, A5E41864807-AB
22.8 mA
22.8 mA