Connect M12 Cable Socket To The Cable - Siemens SITRANS TH100 Operating Instructions Manual

Temperature transmitter with 4to 20 ma/hart
Table of Contents

Advertisement

For devices with a Han plug mounted on the enclosure, make the connection via the cable
socket.
Requirement
• The terminal area of the cable socket is suitable for cables with diameters ranging from 6 to
12 mm.
• These cables use stranded wires with 1 mm
• You are using a crimping tool from HARTING (article number 09 99 000 0110).
Procedure
1. Slide the sleeve and the screwed joint on the cable.
2. Strip approx. 8 mm of the cable ends.
3. Crimp the contact parts on the cable ends.
4. Assemble the cable socket.
Connector pin assignment with Han 7D or
Han 8D plug or cable socket
6.10

Connect M12 cable socket to the cable

Loss of safety required for approval by using the M12 device plug.
You may only use the plug for non-Ex devices; otherwise, the safety required for the approval
is not guaranteed.
Note
A conductive connection must not exist between the shield and the connector housing.
Note
Observe the protection class of the M12 device plug when defining the protection class.
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Operating Instructions, 05/2020, A5E41864807-AB
WARNING
6.10 Connect M12 cable socket to the cable
2
as single conductors ("+", "-" and ground).
I
Output current
A
U
Auxiliary power
H
Connecting
101