Enable The Button Lock On The Display; 9.6 Setting The Fault Current Of The Internal Transmitter With Switch To ≥ 21 Ma - Siemens SITRANS TH100 Operating Instructions Manual

Temperature transmitter with 4to 20 ma/hart
Table of Contents

Advertisement

9.5.2.4

Enable the button lock on the display

Procedure
1. Navigate to the parameter view.
Navigating in the views (Page 107)
2. In the parameter view, select the "Button lock" parameter.
3. Press the
The "EDIT" symbol flashes.
4. Select ON with the
5. Use the
Result
• The display automatically returns to the measurement view.
• The display automatically changes between the measured values every 12 seconds.
• The symbol for button lock "LL" and the measured value ID are displayed alternately.
9.6
Setting the fault current of the internal transmitter with switch to
≥ 21 mA
Introduction
You set the fault current of the internal transmitter from ≤ 3.6 mA to ≥ 21 mA with the switch
on the display.
A fault current ≥ 21 mA is not permissible for operation of the device with functional safety.
Functional safety cannot be activated with a fault current ≥ 21 mA.
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
Operating Instructions, 05/2020, A5E41864807-AB
9.6 Setting the fault current of the internal transmitter with switch to ≥ 21 mA
button.
or
button.
button to confirm.
Parameter assignment
175