7.4.3 Setting Feed-in Power
O O N N : : no power could be fed into the grid.
•
O O F F F F : : all system output power could be fed into the grid.
•
P P a a r r t t i i a a l l : : partial of the output power could be fed into the grid.
•
– When the existing system is disabled, the feed-in power ranges from 0 to the
rated power of the existing system.
– When the existing system is enabled, the feed-in power ranges from (rated
power of the existing system) to ([rated power of the hybrid inverter] + [rated
power of the existing system]).
According to the local regulations in Germany, please set the feed-in power to
70 % of the installation capacity.
For example, with a total maximum installation capacity of 4600 W (SH4K6-30),
the feed-in power should be set to 3220 W (i.e. 4600 * 70 %).
7.4.4 Setting System Time
The correct system time is very important. Wrong system time will directly affect the
data logging and power generation value. The clock is in 24-hour format.
DD, MM, and YY stand for day, month, and year respectively.
•
hh, mm, and ss stand for hour, minute, and second respectively.
•
7.4.5 Setting Backup Function
The backup function is disabled by default.
If the backup function is enabled, you should set the reserved capacity for Li-ion
batteries.