7.8.3 Power Regulation Parameters

Active Power Regulation
Tap "Settings→Power Regulation Parameters→Active Power Regulation" to enter the
screen, as shown in the following figure.
table 7-8 Active Power Regulation
Parameter
Active power soft start
after fault
Active power soft start
time after fault
Active power gradient
control
Active power decline
gradient
figure 7-16 NS Protection(Passive Valid)
figure 7-17 Active Power Regulation
Definition/Setting
Description
The switch for enabling/dis-
abling the soft start function
after a fault occurs.
Time that the soft start takes to
raise the power from 0 to
100% rated power.
Switch for enabling/disabling
the active power rate settable
function.
The decline rate of inverter ac-
tive power per minute.
7 iSolarCloud App
Range
Enable/Disable
1s~1200s
Enable/Disable
1%/min~6000%/min
83