Physical installation
............................................................................................................................................................................................................................................................
Figure 2-7 Mounting bracket position for ETSI frame
........................................................................................................................................................................................................................
12
Determine the position that the rack-mount Alcatel-Lucent 1850 TSS-5 shelf will be
mounted. Start at the bottom of the bay and add shelves from bottom to top.
Note:
Only use heat baffles (848862181) above and below when stacking Alcatel-Lucent
1850 TSS-5 shelves with other vendors equipment in the same bay.
........................................................................................................................................................................................................................
13
Position the rack-mount Alcatel-Lucent 1850 TSS-5 shelf in the frame and secure the
shelf to the frame using the thread-forming screws, included with the shelf.
........................................................................................................................................................................................................................
14
Attach grounding wire between the UL safety ground screw located in the middle of the
power terminal block and appropriate safety ground. See
block" (p.
Note:
shelf (12 AWG).
............................................................................................................................................................................................................................................................
2 - 1 0
There are no heat baffles needed betweenAlcatel-Lucent 1850 TSS-5 shelves.
2-11).
Grounding wire must be of the same gauge as the cables used to power the
Alcatel-Lucent 1850 TSS-5 rack-mount shelf installation
Figure 2-8, "Power terminal
365-372-403R5.1
Issue 1 November 2008