Vega VEGAWAVE 62 Operating Instructions Manual page 21

Vibrating level switch with suspension cable for powders, two-wire 8/16 ma
Table of Contents

Advertisement

Mode on the sensor
Min.
Dry run protection
Min.
Dry run protection
Fault message
(min./max. mode)
Mode on the signal
Level
conditioning in-
strument
Mode A
Overflow protection
Mode A
Overflow protection
Mode B
Dry run protection
VEGAWAVE 62 • Two-wire 8/16 mA
Level
any
VEGAWAVE 62 level switch with signal conditioning instru-
ment
1)
The following table provides an overview of the switching conditions
depending on the adjusted mode of the signal conditioning instru-
ment and the level.
Note:
Keep in mind that the mode switch of VEGAWAVE 62 must be always
set to "max.".
Signal current -
Sensor
approx. 8 mA
approx. 16 mA
approx. 16 mA
You can find suitable signal conditioning instruments in chapter "Technical
1)
data".
Signal current - Sensor
approx. 8 mA
approx. 16 mA
< 2.3 mA
Signal lamp - sen-
sor
Green
Red
Red
6 Setup
Signal lamp - sensor
Green
Red
flashes red
Signal lamp - sig-
nal conditioning
instrument
21

Advertisement

Table of Contents
loading

Table of Contents