BACnet router properties
On the BACnet router properties page, you can change the following properties:
•
IP address of the router in the controller and the system database
•
BACnet routing settings
•
Color and prime variable caching settings
IP Configuration
Allow remote management
of IP configuration
Enable IP configuration
changeover
BACnet Router Options
Ignore all Reject-Message-to-
Network, Reason=1
messages
Color/Prime Variable
Caching
Disable Color Cache
Dead Module Timeout
Carrier® ChillerVu™
(OPN-PSM-MPCXPE)
Installation and Start-up Guide
For future use.
Select to remotely change the router's IP Address, Subnet Mask, and Default
Gateway Address.
Type the new addresses and the UDP Port that your server is using to
communicate to all controllers.
In the Changeover timeout field, enter:
•
0:00 to have the controller use the Next settings as soon as the controller can
communicate with the Next Default Gateway Address.
•
A specific length of time to have the controller use the Next settings as soon as
the controller can communicate with the Next Default Gateway Address, or
when the timeout expires, whichever occurs first.
See "To remotely change a controller's IP address" in i-Vu® Help for more
information on using this feature.
Clear to delete and rediscover a router if a network's router indicates that the
network is no longer present (reason=1).
Select to continue routing messages to a network even if its router indicates that
the network is no longer present.
Clear (enable) to improve responsiveness in retrieving colors.
Select (disable):
•
To reduce network traffic to third-party (non-color-supporting) devices
•
If using the Carrier® ChillerVu™ on the controller network, not as a router
NOTE Selecting this checkbox also disables dead module alarms.
After this period (minutes:seconds) of non-response from a controller, the router
sends an alarm to the server.
Carrier Proprietary and Confidential