Troubleshooting
Before replacing the fuse, try to determine why the fuse blew.
•
Check the Power wiring polarity of the Carrier® ChillerVu™, any attached expanders, and any other controllers
that share the power supply. Use the same polarity for all of them.
•
Verify that outputs are wired to the appropriate types of devices. See Outputs (page 18). For example, you
cannot wire a 24 Vac device to an output.
•
Carrier® ChillerVu™ - If the Aux Power Out port is used, verify that it is wired correctly. See To wire inputs
and outputs (page 18).
To replace the fuse:
Turn off the Carrier® ChillerVu™'s power.
1
If the fuse is on an expander, remove the coverplate.
2
Using needle-nose pliers, pull the bad fuse from the Carrier® ChillerVu™.
3
Cut the wires on the new fuse so that the total length is approximately 1 inch and the fuse is centered.
4
1 inch
Bend the wire ends so that the length is approximately 1/2 inch.
5
1 /
inch
2
Use the pliers to grip one wire end of the fuse and push into a fuse socket on the Carrier® ChillerVu™.
6
Grip the other wire end of the fuse and push into the other fuse socket.
7
If working on an expander, replace the coverplate.
8
Turn on the power and verify that the Power LED is lit.
9
To take the Carrier® ChillerVu™ out of service
If needed for troubleshooting or start-up, you can prevent the i-Vu® application from communicating with the
Carrier® ChillerVu™ by shutting down communication from the controller to the i-Vu® application. When Out of
Service, i-Vu® no longer communicates properties, colors, trends, etc..
On the i-Vu® navigation tree, select the Carrier® ChillerVu™.
1
On the Properties page, check Out of Service.
2
Click Accept.
3
Carrier® ChillerVu™
(OPN-PSM-MPCXPE)
Installation and Start-up Guide
Carrier Proprietary and Confidential
60
CARRIER CORPORATION ©2017
All rights reserved