System Test Menu; Alarm Test; Fault Test; Lamp Test - Notifier Inertia 1010 Operator's Manual

Intelligent fire detection and alarm system
Hide thumbs Also See for Inertia 1010:
Table of Contents

Advertisement

P
12
AGE
During a walk test, as each detector alarms it will not display on the LCD, it's LED will activate for 5 seconds and
outputs set as "Walk Test" will toggle on for 10 seconds then reset. These outputs should be connected to
sounders or bells to confirm to the testing technician that the alarm has been received at the panel.
The detectors will also automatically reset during walk test mode.
NOTE: During walk test, all type ID's are ignored therefore NONA and PHOD detectors will register in walk
tests. Ie: If a door switch or fan airflow module etc. activates it will ring bells for 10 seconds and appear in the
report. MMX-2 modules are not able to be walk tested.
S
T
YSTEM
EST MENU
The System test menu allows for manual testing of devices on the system. To enter system test mode, simply
press the "SYSTEM TEST" button once.
The SYSTEM TEST menu provides the following options:
Selection
Abbreviation
1
ALM
2
FLT
3
Lamp
4

System

P
T
ERIODIC
EST
To ensure correct operation, the panel continually performs a series of automatic chamber
tests on all intelligent detectors installed in the system. If a detector fails one of these
automatic chamber tests, it will generate a Fault message eg; "DET FAILED TEST", "DRIFT
COMPENSATION OUT OF TOLERANCE" etc. These messages signify either the detector
may be incapable of generating an alarm or has become contaminated and may cause a
false alarm. Either way it is important that your service company be contacted immediately to
repair or replace the indicated device.
Please note: While the fire panel carries out this test on a detector, the LED's on the detector
stop blinking for 10 seconds.
Description
A
T
:
LARM
EST
This provides for a real alarm test on a detector. Enter LxxDxx then
press enter. The detector must then be Acknowledged and Reset as per
normal.
F
T
:
AULT
EST
This provides for a real fault test on a detector/ module. Enter LxxDxx or
LxxMxx then enter. You will be required to acknowledge faults as per
normal.
L
T
:
AMP
EST
Initiates a lamp test on the system.
S
:
YSTEM
Function is not used.
C
© 2000, N
I
OPYRIGHT
OTIFIER
1010/2020 O
P
L
NERTIA
TY
TD
M
PERATORS
ANUAL

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Inertia 1010 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Related Products for Notifier Inertia 1010

This manual is also suitable for:

Inertia 2020

Table of Contents