Mounting Kits - Siemens SITRANS VP300 Operating Instructions Manual

Electropneumatic positioners with or without hart
Hide thumbs Also See for SITRANS VP300:
Table of Contents

Advertisement

Description
Dimensions = mm (inches)
Figure 4-3
Procedure
1. Prior to mounting the positioner, remove the cover foil from the pneumatic connections.
2. Screw magnet clamp
3. Fasten the positioner on the interface. Tighten fixing screws
4. Check whether the gap dimensions for the magnet clamp
4.3.3

Mounting kits

Missing equipotential bonding in areas with combustible dust
Danger of explosion.
 Make sure that the device and the control valve are connected with the equipotential
The description is supplied with the relevant mounting kit, and does not form a part of these
operating instructions.
See also
Connecting the device (Page 45)
SITRANS VP300 with or without HART
Operating Instructions, 03/2011, A5E01258666-03
s
Magnet clamp fixing screw
Magnet clamp (contains magnet for contactless measurement of position)
Device fixing screws
Gap dimensions, position of the magnet clamp
picture in section "Dimensions for OPOS interface (VDI/VDE 3847) (Page 31)".
This will result set the gap dimensions specified in the above figure.
WARNING
bonding.
into the M6 threaded hole on the drive axis of the actuator, see
Installing/mounting
4.3 Mounting
with a torque of 8 Nm.
are correct.
33

Advertisement

Table of Contents
loading

Table of Contents