Commissioning
7.4 Settings on the pneumatic block
7.4
Settings on the pneumatic block
Requirement
Torx screwdriver TX20
Introduction
①
②
③
Figure 7-1
Procedure "Adjuster for purging air selector" (purge air)
Factory setting: "IN".
● Turn the adjuster to "IN" to vent the instrument air to the inside and flush the inside of the
● Turn the adjuster to "OUT" to vent the instrument air to the outside.
Procedure "Adjuster for actuator size" (actuator size)
You can set the actuator size in four categories. The adjuster is divided into four grids for this
purpose. Factory setting: bottom, very large actuators.
134
Adjuster for purging air selector (purge air)
Adjuster for actuator size (actuator size)
Adjuster for behavior of device in case of sudden failure of pneumatic auxiliary power
Pneumatic block, schematic
device.
SITRANS VP300 with or without HART