Fan And Pump Control Parameters - Watt Drive V2500 Series Manual

Table of Contents

Advertisement

Group 11: Fan & Pump Control Parameters
Para-
Explanation
meters
11-00
V/F Curve Selection
Start-Up Frequency of the
11-01
Auxiliary Motor
Stop Frequency of Auxiliary
11-02
Motor
Time Delay before Starting the
11-03
Auxiliary Motor
Time Delay before Stopping
11-04
the Auxiliary Motor
Sleep/Wake Up Detection
11-05
Time
11-06
Sleep Frequency
11-07
Wakeup Frequency
Settings
00: V/F Curve determined by Pr.01-00
to Pr.01-06
01: 1.5 Power Curve
02: 1.7 Power Curve
03: Square Curve
04: Cube Curve
0.00 to 120.00 Hz
0.00 to 120.00 Hz
0.0 to 3600.0 sec
0.0 to 3600.0 sec
0.0 ~6550.0 sec
0.00~Fmax
0.00~Fmax
8-15
Factory
Actual
Setting
Setting
00
0.00
0.00
0.0
0.0
0.0
0.00
0.00
8