CHAPTER 5' – QUICK START GUIDE
The parameters of the inverter drives V2500 are pre-set by factory to application based
values that usually occur in standard environment.
When following the Warnings in the Introduction of this manual and the storage and
installation guidelines in chapter 2 as well as the wiring notes in chapter 3, the start-up will
usually be executed in very short time because of the parameters factory settings.
Some parameters that maybe are still necessary to have an eye on are listed right here
below. The complete list of parameters for preparing the inverter for your special
applications' requirements can be found in chapter 8 of this manual or – as a detailed
description - in the long version of the manual, available for download at
www.wattdrive.com.
Groupe 0: User Parameters
Para-
Explanation
meter
00-09 Control Methods
Groupe 1: Basic Parameters
01-00 Maximum Output Freq. (Fmax) 50.00 to 400.00 Hz
Maximum Voltage Frequency
01-01
(Base Freq) (Fbase)
Maximum Output Voltage
01-02
(Vmax)
01-09 Accel Time 1
01-10 Decel Time 1
Groupe 2: Operation Method Parameters
Source of First Frequency
02-00
Command
Settings
00: V/F Control
01: V/F + PG Control (also see Pr.10-09
to 10-11)
02: Vector Control
03: Vector + PG Control (also see
Pr.10-09 to 10-11)
0.10 to 400.00 Hz
230-V-Series: 0,1 V to 255,0 V
400/460-V-Series: 0,1 V to 510,0 V
! 0.01 to 3600.0 sec
! 0.01 to 3600.0 sec
00: Digital keypad or Inc./Dec. Frequ.
01: 0 to +10Vdc from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 communication interface
!
05: RS-485 communication interface. It
won't memorize the frequency.
06: Combined usage of the master and
auxiliary frequency command
02-10, 02-11,02-12
5'-1
5
Factory
Actual
Setting
Setting
02
50.00
50.00
230,0
400,0
10.0
10.0
01