Special Parameters - Watt Drive V2500 Series Manual

Table of Contents

Advertisement

CHAPTER 8: PARAMETER SUMMARY
Group 8: Special Parameters
Para-
Explanation
meters
08-00
DC Braking Current Level
DC Braking Time during
08-01
Start-Up
DC Braking Time during
08-02
Stopping
08-03
Start-Point for DC Braking
Momentary Power Loss
08-04
Operation Selection
Maximum Allowable Power
08-05
Loss Time
08-06
B.B. Time for Speed Search
Current Limit for Speed
08-07
Search
Skip Frequency 1 Upper
08-08
Bound
Skip Frequency 1 Lower
08-09
Bound
Skip Frequency 2 Upper
08-10
Bound
Skip Frequency 2 Lower
08-11
bound
Skip Frequency 3 Upper
08-12
bound
Skip Frequency 3 Lower
08-13
Bound
08-14 Auto Restart After Fault
08-15 Auto Energy Saving
08-16 AVR Function
Software Setting of the
08-17
Braking Level
08-18 Base-block Speed Search
08-19 Speed Search
Speed Search Frequency
08-20
during Start-up
Auto Reset Time at Restart
08-21
after Fault
Compensation Coefficient for
08-22
Motor Instability
00 to 100%
0.0 to 60.0 Sec
0.0 to 60.0 Sec
0.00 to 400.00 Hz
00: Operation stops after Momentary
Power Loss
01: Operation continues after Momentary
Power Loss, speed search starts with
Master Frequency
02: Operation continues after Momentary
Power Loss, speed search starts with
Minimum Output Frequency
0.1 to 5.0 sec
0.1 to 5.0 sec
30 to 200%
0.00 to 400.00 Hz
0.00 to 400.00 Hz
0.00 to 400.00 Hz
0.00 to 400.00 Hz
0.00 to 400.00 Hz
0.00 to 400.00 Hz
00 to 10
00: Disable
01: Enable
00: AVR Function Enable
01: AVR Function Disable
02: AVR Function Disable for Decel
230V: 370 to 430V
460V: 740 to 860V
00: Speed Search Starts with Last
Frequency Command
01: Starts with Minimum Output
Frequency (Pr. 01-05)
00: Speed Search Disable
01: Speed Search Enable
00: Setting Frequency
01: Maximum Operation Frequency
!
(01-00)
00 to 60000 sec
0~1000
!
8-12
Settings
Factory
Actual
Setting
Setting
00
0.0
0.0
0.00
00
2.0
0.5
150
0.00
0.00
0.00
0.00
0.00
0.00
00
00
00
380
760
00
00
00
600
0