Group 6: Protection Parameters
Para-
Explanation
meters
Over-Voltage Stall Prevention
06-00
Level
Over-Current Stall Prevention
06-01
during Accel
Over-Current Stall Prevention
06-02
during Operation
Over-Torque Detection Mode
06-03
(OL2)
06-04
Over-Torque Detection Level
06-05
Over-Torque Detection Time
Electronic Thermal Overload
06-06
Relay Selection
Electronic Thermal
06-07
Characteristics
06-08
Present Fault Record
Second Most Recent Fault
06-09
Record
Third Most Recent
06-10
Fault Record
Settings
230V-series: 330V ~ 410V
400/460V-series: 660V ~ 820V
0: Disable
20 to 250%
CAUTION: High current will reduce the
inverters lifetime and/or may
cause immediate damage.
20 to 250%
CAUTION: High current will reduce the
inverters lifetime and/or may
cause immediate damage.
00: Disabled
01: Enabled during constant speed
operation and operation continues
after over-torque detection.
02: Enabled during Constant Speed
Operation and operation halted
after over-torque detection
03: Enabled during Accel and continues
operation after over-torque
detection
04: Enabled during Accel and halted
after over-torque detection
10 to 200%
NOTE: High current will reduce the
inverters lifetime and/or may
cause immediate damage.
0.1 to 60.0 Sec
00: Standard Motor (self ventilated)
01: Special Motor (force cooled)
02: Disabled
30 to 600 Sec
00: No Fault occurred
01: Over Current (oc)
02: Over Voltage (ov)
03: Over Heat (oH)
04: Over Load (oL)
05: Over Load (oL1)
06: External Fault (EF)
07: IGBT Protection (occ)
08: CPU failure (cF3)
09: Hardware Protection Failure (HPF)
10: Current exceed during Acceleration
(ocA)
11: Current exceed during Deceleration
(ocd)
12: Current exceed during Steady State
(ocn)
13: Ground Fault (GFF)
14: Low Voltage (Lv)
15: CPU READ failure CF1
8-9
Factory
Actual
Setting
Setting
390*
170
170
00
8
150
0.1
00
60
00