Watt Drive V2500 Series Manual page 35

Table of Contents

Advertisement

Para-
Explanation
meter
Groupe 5: Multi-Step Speed and PLC Parameters
Groupe 6: Protection Parameters
Groupe 7: Motor Parameters
07-00
Motor Rated Current
07-01
Motor No-Load Current
07-04
Number of Motor Poles
07-05
Motor Auto Detection
Groupe 8: Special Parameters
Groupe 9: Communication Parameters
Groupe 10: PID Control Parameters
10-10
PG Pulse Range
10-11
PG Input
Groupe 11: Fan & Pump Control Parameters
11-00
V/F Curve Selection
Settings
26: Forced Stop (N.O.)
27: Parameter lock enable (N.C.)
(Open: Lock, Close: Unlock)
28: PID function disabled
29: Jog Fwd/Jog Rev (it is enabled at
external terminal JOG command)
30: Reset (N.C)
31: Source of second frequency
command enabled
32: Source of second operation
command enabled
33: One shot (PLC)
34: Proximity sensor input for Index
function (see Pr. 04-23 to 04-25)
35: Output Shutoff Stop (N.O.)
36: Output Shutoff Stop (N.C)
00: No functions
30 to 120% (of AC drive output current)
0 to 90% (of AC drive output current –
less than Pr.07-00)
2 to 10
00: Disable
01: Enable static motor detection
(+ press RUN key)
02: Enable dynamic motor detection
(+ press RUN key)dynamic
WARNING: Motor must run free!!
01 to 40000
00: Disable PG
01: Single phase
02: Forward / Counterclockwise rotation
03: Reverse / Clockwise rotation
00: V/F Curve determined by Pr.01-00
to Pr.01-06
01: 1.5 Power Curve
02: 1.7 Power Curve
03: Square Curve
04: Cube Curve
5'-3
Factory
Actual
Setting
Setting
5
100
40
4
00
1024
00
00

Advertisement

Table of Contents
loading

Table of Contents