Group 9: Communication Parameters
Para-
Explanation
meters
09-00 Communication Address
09-01 Transmission Speed
Transmission Fault
09-02
Treatment
09-03 Timeout Detection
09-04 Communication Protocol
09-05 HMI Register 1
09-06 HMI Register 2
Response Delay Time after
09-07
AC-drives receives
communication command
Settings
! 1 to 254
00: Baud Rate 4800bps
01: Baud Rate 9600bps
!
02: Baud Rate 19200bps
03: Baud Rate 38400bps
00: Warn and keep Operating
01: Warn and Ramp to Stop
02: Warn and Coast to Stop
!
03: No warning and keep Operating
0.0 ~ 60.0 second
!
0.0: Disable
00: 7,N,2 (Modbus, ASCII)
01: 7,E,1 (Modbus, ASCII)
02: 7,O,1 (Modbus, ASCII)
!
03: 8,N,2 (Modbus, RTU)
04: 8,E,1 (Modbus, RTU)
05: 8,O,1 (Modbus, RTU)
! 00 to 65535
! 00 to 65535
00 ~ 200ms
8-13
Factory
Actual
Setting
Setting
1
01
03
0.0
00
00
00
00
8