≥ 40
≥ 40
Position:
1
Fire damper
2
Solid ceiling construction
3
Stuffing box (mineral stone wool min. density 150 kg/m³)
4
Fire protection coating th. 1 mm
5
Fire protection mastic th. 1 mm
6
Duct
*
* min. 110 - Concrete/ min. 125 - Aerated concrete
Used materials - example:**
3
HILTI CFS-CT B 1S 140/50 or
ROCKWOOL HARDROCK + coating HILTI CFS-CT
4
HILTI CFS-CT
5
HILTI CFS-S ACR
** Fire resistant insulation and fire resistant board can be
replaced by another approved fire sealing system for
damper installation with equivalent material properties.
19