Levelflex FMP51 Modbus
Measured variable
Measuring range
Media group
DC (ε
)
r
1
1.4...1.6
2
1.6...1.9
3
1.9...2.5
4
2.5...4
5
4...7
6
> 7
1)
The measuring range for interface measurement is limited to 10 m (33 ft).
2)
optionally available for FMP51
Endress+Hauser
Input
The measured variable is the distance between the reference point and the product surface.
Subject to the empty distance entered "E" the level is calculated.
Alternatively, the level can be converted into other variables (volume, mass) by means of
linearization (32 points).
The following table describes the media groups and the possible measuring range as a function of
the media group.
Typical liquids
condensed gases, e.g. N
, CO
2
2
• liquefied gas, e.g. propane
• solvent
• Freon
• palm oil
mineral oils, fuels
• benzene, styrene, toluene
• furan
• naphthalene
• chlorobenzene, chloroform
• cellulose spray
• isocyanate, aniline
• aqueous solutions
• alcohols
• ammonia
• Reduction of the max. possible measuring range through buildup, above all of moist products.
• Due to the high diffusion rate of ammonia it is recommended with gas-tight bushing
measurements in this medium.
Levelflex FMP51
bare metallic
rod probes
on request
•
one-piece: 4 m (13 ft)
15 to 22 m (49 to 72 ft)
•
divisible: 10 m (33 ft)
•
one-piece: 4 m (13 ft)
22 to 32 m (72 to 105 ft)
•
divisible: 10 m (33 ft)
•
one-piece: 4 m (13 ft)
•
divisible: 10 m (33 ft)
•
one-piece: 4 m (13 ft)
•
divisible: 10 m (33 ft)
•
one-piece: 4 m (13 ft)
•
divisible: 10 m (33 ft)
1)
Measuring range
bare metallic
rope probes
32 to 42 m
(105 to 138 ft)
42 to 45 m
(138 to 148 ft)
45 m (148 ft)
coax probes
6 m (20 ft)
6 m (20 ft)
6 m (20 ft)
6 m (20 ft)
6 m (20 ft)
6 m (20 ft)
2)
for
13