Mounting The Keypads; Supplementary Power For Additional Keypads - ADEMCO N7227V5 Installation And Setup Manual

Vista security system installation and setup guide
Hide thumbs Also See for Ademco N7227V5:
Table of Contents

Advertisement

VISTA-10SE Installation and Setup Guide
Wiring Run Chart for Devices* Drawing Aux Power From the Control (12V+ & 12V–)
Wire Size
#22
#20
#18
#16
*
Includes keypads, RF receivers, relay units, and 4285/4286 VIP Modules.
The length of all wire runs must not exceed 1500 feet (457m) when unshielded quad conductor
cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect
on the data lines when quad cable is used.
2. Run field wiring from the control to the keypads (using standard 4-conductor twisted
wire cable using the wire gauge determined in step 1).
3. Connect remote keypads to terminals 4, 5, 6, and 7 on the control board, as shown in
Figure 5.

Mounting the Keypads

1. Make sure addressable-type keypads (6128, 6137, 6138, and 6139) are set to non-
addressable mode (address 31), which is the factory default setting. Refer to the
instructions provided with the keypad for address setting procedure.
2. Mount the keypads at a height that is convenient for the user. Refer to the instructions
provided with the keypad for mounting procedure.
You can either surface mount or flush mount keypads (using an appropriate Trim Ring
Kit: 6139TRK). Refer to the mounting instructions and template included with the
keypad and/or trim ring kit for specific information.

Supplementary Power for Additional Keypads

The control provides 500mA for powering keypads (up to a maximum of 4) and other devices
from the auxiliary power output. The backup battery will supply power to these keypads in
the event that AC power is lost.
When the control's auxiliary power load for all devices exceeds 500mA, you can power
additional keypads from a regulated, 12VDC power supply (e.g., 487-12 supplies 12V, 250mA;
488-12 supplies 12V, 500mA). Use a UL Listed, battery-backed supply for UL installations.
The 487-12/488-12 power supplies have a backup battery that can power these keypads in the
event of AC power loss.
3-2
TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
50mA or less
500 ft (152m)
750 ft (228.6m)
1300 ft (396m)
1500 ft (457m)
KEYPAD CONNECTOR CABLE
BLACK
4
RED
5
GREEN
6
YELLOW
7
CONTROL
TERMINALS
Figure 5. Keypad Connections to the Control Board
100mA
250 ft (76m)
80 ft (24m)
380 ft (116m)
130 ft (39.6m)
650 ft (198m)
220 ft (67m)
1000 ft (305m)
330 ft (100.5m)
KEYPADS
300mA
500mA
50 ft (15m)
80 ft (24m)
130 ft (39.6m)
200 ft (70m)
V10SE-026-V0