Counter node
Hide thumbs Also See for SureCross DX80 FlexPower:

Advertisement

Counter Inputs
Threshold: 1.5V or 0.25V (Sinking or sourcing selected
inputs require the 1.5V threshold setting)
Debouce: DIP Switch Selectable. Enable debounce to
filter a noisy input signal that may lead to false triggers.
Event Counter: Input rating 1 Hz to 10 kHz (For battery
powered devices, the recommended input rating is less
than 1 kHz)
Rate (Frequency) Counter: 1 Hz to 25 kHz
Threshold (sinking counter on Performance and Multi-
Hop models) : 1.7V
Discrete Inputs
One, selectable
Rating: 3 mA max current at 30V dc
Sample/Report Rates: 125 milliseconds
Discrete Input ON Condition
PNP: Greater than 8V
NPN: Less than 0.7V
Rating
IEC IP67; NEMA 6; (See UL section below for any ap-
plicable UL specifications)
Operating Conditions
Operating Temperature: −40 to +85 °C (Electronics);
−20 to +80 °C (LCD)
Operating Humidity: 95% max. relative (non-condens-
ing)
Radiated Immunity: 10 V/m, 80-2700 MHz
(EN61000-6-2)
Refer to the
SureCross DX80 Wireless I/O Network Product Manual
ing the devices at the maximum operating conditions for extended periods can shorten the life of the device.
Included with Device (Integrated Battery)
• BWA-HW-001: Mounting Hardware Kit, containing four M5-0.8 x 25mm SS screws, four M5-0.8 x 16mm SS screws, four M5-0.8mm
SS hex nuts, and four #8-32 x 3/4" SS bolts
• BWA-9O2-C (900 MHz) or BWA-2O2-C (2.4 GHz): Antenna, 2 dBd Omni, Rubber Swivel RP-SMA Male. (Not included with Internal
antenna models)
• Quick Start Guide (128185 for DX80 Gateways or 152653 for MultiHop models)
Warnings
Antenna Installations. Install and properly ground a qualified surge suppressor when installing a remote antenna system. Remote antenna
configurations installed without surge suppressors invalidate the manufacturer's warranty. Keep the ground wire as short as possible and make all
ground connections to a single-point ground system to ensure no ground loops are created. No surge suppressor can absorb all lightning strikes; do
not touch the SureCross® device or any equipment connected to the SureCross device during a thunderstorm.
Exporting SureCross Radios. It is our intent to fully comply with all national and regional regulations regarding radio frequency emissions. Custom-
ers who want to re-export this product to a country other than that to which it was sold must ensure the device is approved in the destina-
tion country. A list of approved countries appears in the Radio Certifications section of the product manual. The SureCross wireless products were
certified for use in these countries using the antenna that ships with the product. When using other antennas, verify you are not exceeding the transmit
power levels allowed by local governing agencies. Consult with Banner Engineering Corp. if the destination country is not on this list.
8
Inputs and Outputs
Discrete Input OFF Condition
PNP: Less than 5V
NPN: Greater than 2V or open
Discrete Outputs
Update Rate: 1 second
ON Condition: Less than 0.7V
OFF Condition: Open
Output State Following Timeout: OFF
Discrete Output Rating (NMOS)
Less than 10 mA max current at 30V dc
ON-State Saturation: Less than 0.7V at 20 mA
Environmental and Certifications
Shock and Vibration
IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz
(p/n 132607) for installation and waterproofing instructions. Operat-
www.bannerengineering.com - tel: 763-544-3164
SureCross DX80 FlexPower Counter Node
P/N 136972 Rev. F