Counter node
Hide thumbs Also See for SureCross DX80 FlexPower:

Advertisement

Debounce. Debounce establishes how to examine a signal's transitions. The factory de-
fault setting is to activate the input filtering to compensate for unclean state transitions.
To turn off the input filtering, set the switch to the ON position.
Inputs. Counter switches 6 and 7 define the inputs as self-energized, sinking (NPN), or
sourcing (PNP). A self-energized input does not require pull-up or pull-down devices for
proper operation. A magnetic pick-up is a self-energized input. The input threshold can
be adjusted to compensate for low amplitude signals.
Threshold. The counter has a selectable input threshold of 0.25V or 1.5V. For sinking
(NPN) or sourcing (PNP) inputs, set the threshold to 1.5V.
Storage Mode and Sleep Mode
While in storage mode, the radio does not operate. All SureCross® radios powered from an integrated battery ship from the factory in
storage mode to conserve the battery. To wake the device, press and hold button 1 for five seconds. To put any FlexPower® or integra-
ted battery SureCross radio into storage mode, press and hold button 1 for five seconds. The radio is in storage mode when the LEDs
stop blinking, but in some models, the LCD remains on for an additional minute after the radio enters storage mode. After a device has
entered storage mode, you must wait one minute before waking it.
During normal operation, the SureCross radio devices enter sleep mode after 15 minutes of operation. The radio continues to function,
but the LCD goes blank. To wake the device, press any button.
Wiring for Integrated Battery Counter Models
5-Pin M12 Euro-style Connection
2
3
1
5
4
Discrete Input Wiring for PNP Sensors
PWR
10-30V dc
DIx
LED Behavior for the Nodes
After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. A Node will not sample its
inputs until it is communicating with its Gateway. When testing communication between the Gateway and Node, all radios and antennas
should be at least two meters apart or the communications may fail.
LED 1
(flashing green)
(flashing red)
4
Pin #
Description
1
brown, open (+10 to 30V dc)
2
white, counter
3
blue, dc common (GND)
4
black, NMOS Discrete OUT (DO1)
5
gray, Discrete IN (DI1)
Discrete Input Wiring for NPN Sensors
DIx
GND
dc common
LED 2
(flashing red)
(flashing red, 1 per 3 sec)
www.bannerengineering.com - tel: 763-544-3164
SureCross DX80 FlexPower Counter Node
Device switches
Discrete Output Wiring (NPN or NMOS)
PWR
DOx
Load
GND
Node Status
Radio Link Ok
Device Error
No Radio Link
P/N 136972 Rev. F
Counter switches
10-30V dc
dc common