Basic Settings - Huawei NetCol5000-A035 Quick Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

11
Power-On
Power-On
11.1
1. Subsequently switch on main control board power circuit breaker QF8 and general circuit breaker
QF1.
2. Measure the controller loop voltage by using a voltmeter. Ensure that the control voltage is within
the range of 24 V AC (tolerance ±10%).

Basic Settings

11.2
For initial power-on, the system enters the quick setting screen. Set the Language, Date format,
Date, Time, Zone, Monitor mode, and verifying the present voltage. For non-initial power-on, the
LCD automatically enters the home screen.
Temperature and Humidity Settings
11.3
NOTE
1. Users include Admin, Engineer, Operator, and Guest. The Admin users have the highest
permission, followed by the Engineer, Operator, and Guest users. The initial passwords for the
Admin, Engineer, and Operator users are all 000001. The Guest user does not have a initial
password. For system security purposes, change the preset password upon first login.
2. After login to the system using a user name, the user right is valid when you touch the screen all
the time. If you do not touch the screen, the user right is only valid for 3 minutes. To ensure
security, manually log out by tapping
On the main screen, tap Settings > System Settings > T/H Sensor to change temperature and
humidity control types or set points.
NOTE
To set T/H control type, Temp control mode, cold aisle sensors 1, 2, and 3, and hot aisle sensors
1, 2, and 3, log in as the Engineer user. To set other parameters, log in as the Operator user.
at the right corner of the home screen.
23