Preparing Materials - Huawei NetCol5000-A035 Quick Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A035:
Table of Contents

Advertisement

NetCol500-A036
2

Preparing Materials

Materials
Cable ties, OT terminals, cord end terminals, voltage jumpers, water sensor and their
Configured
components, teamwork cable, hose clamps, pipe accessories, expansion bolts, and
with the
a humidity and temperature (T/H) sensor.
Equipment
Mandator
y item
Engineering
Procurement
Optional
item
Vacuum pump: 7.2-14.4 m³/h, absolute vacuum ≤ 60 Pa (recommended).
Pressure gauge (measure range is greater than 4.0 MPa), leather hose (tolerance
Special
range is greater than 4.5 MPa), dedicated for R410A.
Tools and
Welding torch and welding rod: silver copper welding rod (containing 5% silver).
Materials
Nitrogen reducing valve: A reducing valve is recommended to install to the outlet
of the nitrogen steel vessel, and the reducing valve range ≥ 4.0 MPa.
Dry nitrogen.
Refrigera
Pipe components (including copper pipes, thermal insulation
nt pipeline
foam, oil traps, and inverted traps) and pipe supports.
Thermal insulation foam and hard pipe conversion adapters
(BSPT 1/2 in., connecting to external threads) + hard pipes
Waterway
(using PP-R or C-PVC materials) or pagoda connectors +
hoses (inner diameter: 3/4 in., using EPDM materials),
thermal insulation foam on waterway.
Power cables and on/off signal cables for the indoor and
Cable
outdoor units.
Humidity and temperature sensors and cables outside the
Cable and
cabinet, indoor unit racks (determined by actual scenarios),
base
and outdoor unit racks or concrete bases (determined by
actual scenarios).
2