5.6
(Optional) Installing the Sunshade (Applied to NetCol500-A072)
6

Connecting Water Pipes

Configuration
Condensate pump, heater,
and humidifier
Condensate pump. No
heater or humidifier
Heater and humidifier. No
condensate pump
No condensate pump,
heater or humidifier
Connecting method
(1) Conversion adapter (2) Hard pipe (3) Pagoda connector
(4) Hose clamp (5) Hose (6) Conversion adapter (7) Hard pipe
Pipes to Be Connected
Humidifier water inlet pipe,
condensate pump drainpipe,
and self-drainpipe (optional)
Condensate pump drainpipe
and self-drainpipe (optional)
Humidifier water inlet pipe and
self-drainpipe
Self-drainpipe
14
Remarks
1. Optional: If there are raised floors
or racks, connect the self-drainpipe.
Otherwise, you are not required to
connect the self-drainpipe.
2. The pump lift is 3.5 m.
3. Condensate pump drainpipe and
self-drainpipe should not be
connected together to avoid water
in the self-drainpipe flowing back to
the pump.