Termination; Fig. 7-5: Pin Assignment Tty / 20 Ma, Active - Bosch Rexroth IndraControl VCP 05 Project Planning Manual

Table of Contents

Advertisement

R911299726 / 02 | Rexroth IndraControl VCP 05
Interfaces

7.1.1.2 Termination

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Electric Drives and Controls | Bosch Rexroth AG
Pin Designation Function
10
T+
Transmitted Data, Positive Polarity
12
S1+
Power Source 1, Positive Polarity
13
R+
Received Data, Positive Polarity
14
R-
Received Data, Negative Polarity
16
S2+
Power Source 2, Positive Polarity
19
T-
Transmitted Data, Negative Polarity
21
S1-
Current Sink 1, Negative Polarity
24
S2-
Current Sink 2, Negative Polarity

Fig. 7-5: Pin assignment TTY / 20 mA, active

The D-SUB connector strips must be shielded sufficiently. See chapter
"Shielding D-SUB Connectors" on page 7-22.
When channel SER1 is operated as a current loop, the termination for
the RS485 must be OFF.
7-5