7.1.2.1 Pin Assignment

7.1.2.2 Termination

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
The interface is suitable for point-to-point and for multi-point connec-
tions.
The wires belonging together are marked with „A" and „B". Some
descriptions refer to the pins with „+" and „-" , where A = + and B = -.
Signal Logic 1
U
Signal Logic 0
U

Fig. 7-6: 25 pin D-SUB female connector strip

Connector in the small operator terminal: 25-pin D-SUB female con-
nector strip
Pin Designation Function
8
T(A)
Transmitted data (+)
9
T(B)
Transmitted data (-)
11
SGND
Signal Ground
22
R(A)
Received data (+)
23
R(B)
Received data (-)

Fig. 7-7: Pin assignment RS485

The D-SUB connector strips must be shielded sufficiently. See chapter
"Shielding D-SUB Connectors" on page 7-22.
For point-to-point connections, always activate the termination. For
multi-point connections, only activate the termination at the cable end.
Rexroth IndraControl VCP 05 | R911299726 / 02
- U
<= -0.3 V i.e. (U
A
B
A
- U
>= +0.3 V i.e. (U
A
B
< U
)
B
> U
)
A
B