Exadata Storage Expansion Rack X5-2 Configuration Restrictions - Oracle Exadata X5-2 Installation Manual

Extreme flash installation guide
Hide thumbs Also See for Exadata X5-2:
Table of Contents

Advertisement

Exadata Storage Expansion Rack X5-2 Configuration Restrictions

Up to 22 servers can be installed in the rack, within a total of 38 rack units.
At least three storage servers must be installed in the rack.
Up to 18 Exadata Storage Servers are supported in the rack. In this configuration, there are
two database servers installed in the rack.
Rack units U01, U20, U21, and U22 are reserved for the Cisco and Sun Datacenter
InfiniBand Switch 36 switches.
Database servers are installed in the rack in the following order:
1. Up to 4 servers in U16 to U19, starting with U16.
2. Up to 4 servers in U23 to U26, starting with U23.
3. Up to 7 servers in U39 to U27, starting with U39. The servers in these rack units are
4. Up to 7 servers in U14 to U02, starting with U14. The servers in these rack units are
Exadata storage servers are installed in the rack in the following order:
1. Up to 3 storage servers in U02 to U07, starting with U02.
2. Up to 4 storage servers in U08 to U15, starting with U08.
3. Up to 7 storage servers in U27 to U40, starting with U27.
4. Up to 2 storage servers in U26 to U30, starting with U26 (if no Database servers
5. Up to 2 storage servers in U19 to U16, starting with U19 (if no Database servers
6. 1 storage server in U41 to U42.
Exadata Storage Expansion Rack X5-2 Configuration
Restrictions
The following restrictions apply to Oracle Exadata Storage Expansion Rack X5-2 flexible
configurations:
Up to 19 Exadata storage servers are supported in the rack.
Oracle Exadata Storage Expansion Rack X5-2 cannot be converted to Oracle Exadata
Database Machine X5-2 rack.
Rack units U01, U20, U21, and U22 are reserved for the Cisco and Sun Datacenter
InfiniBand Switch 36 switches.
Exadata storage servers are installed in the rack in the following order:
22
Oracle Exadata Storage Server X5-2 Extreme Flash Installation Guide • July 2018
separated by 1 rack unit, with solid fillers between the servers.
separated by 1 rack unit, with solid fillers between the servers. No Exadata storage
servers are installed in the rack.
installed in these rack units).
installed in these rack units).