Appendix B. Vendor Information - ClimateWorx
NOTE: All Modbus TCP/IP registers are the same as the Modbus RTU registers for the serial device. If this point list is needed, contact the OEM. The
Modbus TCP/IP node address of the device is also the same as the Modbus RTU node address.
Appendix B.1.
M52 Controller Modbus RTU Mappings to BACnet, Metasys N2, Modbus TCP/IP and LonWorks
Software Version
Voltage
%
Refrigeration Circuit 1 Suction Pressure
psia
Refrigeration Circuit 1 Head Pressure
psig
Refrigeration Circuit 2 Suction Pressure
psia
Refrigeration Circuit 2 Head Pressure
psig
Chilled Water Entering Temperature 1
10 x C/F
Chilled Water Leaving Temperature 1
10 x C/F
Chilled Water Entering Temperature 2
10 x C/F
Chilled Water Leaving Temperature 2
10 x C/F
Circuit 1 Filter Drier Entering Temp
10 x C/F
Circuit 1 Filter Drier Leaving Temp
10 x C/F
Circuit 1 Filter Drier Entering Temp
10 x C/F
Circuit 1 Filter Drier Leaving Temp
10 x C/F
Return Air Temperature
10 x C/F
Return Air Humidity
10 x %RH
Supply Air Temperature
10 x C/F
Supply Air Humidity
10 x %RH
Fan Run Time
Hours
Compressor 1 Run Time
Hours
Compressor 2 Run Time
Hours
Heater 1 Run Time
Hours
Heater 2 Run Time
Hours
Heater 3 Run Time
Hours
Humidifier Run Time
Hours
Cooling Run Time
Hours
Unit Type
0,1,2
EC Fan Speed
%
Reheat Demand
%
De-humidification/ Cooling Demand
%
Humidification Demand
%
Circuit 1 Water Regulating Valve Signal
%
Units
Analog Values (Read Only)
AI
1
x
x
x
x
x Current Firmware Version
AI
2
x
x
x
x
x
AI
3
o
o
o
o
AI
4
o
o
o
o
Requires pressure transducer
AI
5
do do do do
AI
6
do do do do
AI
7
o
o
o
o
AI
8
o
o
o
o
AI
9
o
o
o
o
AI 10 o
o
o
o
Requires sensor kit
AI 11
o
o
o
o
AI 12
o
o
o
o
AI 11
do do do do
AI 12
do do do do
AI 15 x
x
x
x
x
AI 16 x
x
x
x
x
AI 17 o
o
o
o
o
Requries sensor designated as supply air
AI 18 o
o
o
o
o
AI 19 x
x
x
x
x
AI 20
x
x
x
x
AI 21
d
d
d
d
AI 22 o
o
o
o
o
For Staged Reheat only, not on machines
AI 23 o
o
o
o
o
with SCR control
AI 24 o
o
o
o
o
AI 25 o
o
o
o
o
AI 26 x
x
x
x
x
AI 27 x
x
x
x
x Single, Dual, CHW
AI 28 o
o
o
o
o Machines with EC fans
AI 29 o
o
o
o
o
AI 30 o
o
o
o
o
AI 31 o
o
o
o
o
Requires pressure transducer & modulating
AI 32
o
o
o
valve
Notes
Point Name
Software ver.
Voltage
Pressure.Low1
Pressure.High1
Pressure.Low2
Pressure.High2
CW.EWT1
CW.LWT1
CW.EWT2
CW.LWT2
Temp.FilterDriveA1
Temp.FilterDriveB1
Temp.FilterDriveA2
Temp.FilterDriveB2
Temp.ReturnAir
Hum.ReturnAir
Temp.SupplyAir
Hum.SupplyAir
Fan runtime
Comp.1 runtime
Comp.2 runtime
Heater1 runtime
Heater2 runtime
Heater3 runtime
Humid. Runtime
Cooling runtime
UnitStatus
Main-AO01
Main-AO02
Main-AO03
Main-AO04
EX-AO01
Page 38 of 46
ClimateWorx ProtoNode Start-up Guide
Lon Name
Lon SNVT
AI
1
AI
1 nvoSW_Ver_XXX
SNVT_count_f
AI
2
AI
2 nvoVoltage_XXX
SNVT_count_f
AI
3
AI
3 nvoPrs_Lo1_XXX
SNVT_count_f
AI
4
AI
4 nvoPrs_Hi1_XXX
SNVT_count_f
AI
5
AI
5 nvoPrs_Lo2_XXX
SNVT_count_f
AI
6
AI
6 nvoPrs_Hi2_XXX
SNVT_count_f
AI
7
AI
7 nvoCW__wt1_XXX
SNVT_count_f
AI
8
AI
8 nvoCW_Lwt1_XXX
SNVT_count_f
AI
9
AI
9 nvoCW_Ewt2_XXX
SNVT_count_f
AI 10 AI 10 nvoCW_Lwt2_XXX
SNVT_count_f
AI 11 AI 11 nvoTpFlDrA1_XXX
SNVT_count_f
AI 12 AI 12 nvoTpFlDrB1_XXX
SNVT_count_f
AI 13 AI 13 nvoTpFlDrA2_XXX
SNVT_count_f
AI 14 AI 14 nvoTpFlDrB2_XXX
SNVT_count_f
AI 15 AI 15 nvoTmpRetAr_XXX
SNVT_count_f
AI 16 AI 16 nvoHumRetAr_XXX
SNVT_count_f
AI 17 AI 17 nvoTmpSupAr_XXX
SNVT_count_f
AI 18 AI 18 nvoHumSupAr_XXX
SNVT_count_f
AI 19 AI 19 nvoFanRunTm_XXX
SNVT_count_f
AI 20 AI 20 nvoCmp1RnTm_XXX
SNVT_count_f
AI 21 AI 21 nvoCmp2RnTm_XXX
SNVT_count_f
AI 22 AI 22 nvoHt1RunTm_XXX
SNVT_count_f
AI 23 AI 23 nvoHt2RunTm_XXX
SNVT_count_f
AI 24 AI 24 nvoHt3RunTm_XXX
SNVT_count_f
AI 25 AI 25 nvoHumRunTm_XXX
SNVT_count_f
AI 26 AI 26 nvoCoolRnTm_XXX
SNVT_count_f
AI 27 AI 27 nvoUnitStat_XXX
SNVT_count_f
AI 28 AI 28 nvoMainAO01_XXX
SNVT_count_f
AI 29 AI 29 nvoMainAO02_XXX
SNVT_count_f
AI 30 AI 30 nvoMainAO03_XXX
SNVT_count_f
AI 31 AI 31 nvoMainAO04_XXX
SNVT_count_f
AI 32 AI 32 nvoEx_AO01_XXX
SNVT_count_f
30001
30002
30003
30004
30005
30006
30007
30008
30009
30010
30011
30012
30013
30014
30015
30016
30017
30018
30019
30020
30021
30022
30023
30024
30025
30026
30027
30028
30029
30030
30031
30032