Specification Of Power Cord And Air Switch; Wiring Of The Electric Control Cabinet - Gree A Series Service Manual

Modular-type air-cooled (heat pump) chiller
Table of Contents

Advertisement

A Series Modular-type Air-cooled (Heat Pump) Chiller
5.6.3

Specification of Power Cord and Air Switch

See the table below for selection of the power lines and the air switches.
Model
LSQWRF35VM/
NaA-M
LSQWRF60VM/
NaA-M
LSQWRF65VM/
NaA-M
Notes:
(1)The specifications of the breaker and power cable listed in the table above are
determined based on the maximum power (maximum amps) of the unit.
(2)The specifications of the power cable listed in the table above are applied to the conduit-
guarded multi-wire copper cable (like, JYV copper cable, consisting of PV insulated wires
and a PVC cable jacket) used at 45℃ and resistible to 90℃(GB/T 16895.15-2002). If the
working condition changes, they should be modified according to the related national
standard.
(3)The specifications of the breaker listed in the table above are applied to the breaker with
the working temperature at 40℃. If the working condition changes, they should be
modified according to the related national standard.
5.6.4

Wiring of the Electric Control Cabinet

■ LSQWRF35VM/NaA-M,LSQWRF60VM/NaA-M, LSQWRF65VM/NaA-M
Power Supply
380V~415VAC 3Ph
50Hz
380V~415VAC 3Ph
50Hz
380V~415VAC 3Ph
50Hz
Min. sectional area of the
power cable(mm
Live
Neutral
Line
Line
6
6
16
16
16
16
90
Capability of the
2
Air Switch Live
Earth
(A)
Line
6
32
16
63
16
63

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lsqwrf35vm/naa-mLsqwrf60vm/naa-mLsqwrf65vm/naa-m

Table of Contents