D Series Modular Air-cooled Scroll Chillers

6 Electric Control Cabinet

6.1 Wiring for Output Control Lines

Note:
The output control lines of the auxiliary electric heater 1, auxiliary electric heater 2 and the water pump
AC contactor are allowed to the terminal boards 11/12/13/14/15/16 of any module.

6.2 Specification of Power Cord and Air Switch

Model
LSQWRF65M/D-M
LSQWRF65M/NaD-M
LSQWRF80M/D-M
LSQWRF80M/NaD-M
LSQWRF130M/D-M
LSQWRF130M/NaD-M
LSQWRF160M/D-M
LSQWRF160M/NaD-M
Notes:
(a) The specifications of the breaker and power cable listed in the table above are determined based on
the maximum power (maximum amps) of the unit.
(b) The specifications of the power cable listed in the table above are applied to the conduit-guarded multi-
wire copper cable (like, JYV copper cable, consisting of PV insulated wires and a PVC cable jacket)
used at 40℃ and resistible to 90℃ (see IEC60364-5-523:1999). If the working condition changes, they
should be modified according to the related national standard.
(c) The specifications of the breaker listed in the table above are applied to the breaker with the working
temperature at 40℃ . If the working condition changes, they should be modified according to the related
national standard.
Power Supply
380-415V 3N 50Hz
Min. sectional area of
the power cable (mm
Live Line
Neutral Line
16
16
25
16
50
25
70
35
31
Capability of
2
)
the Air Switch
(A)
Earth Line
16
63
16
80
25
125
35
160