2. Remove
power lines and
the electric
heater.
3. Disconnect
power lines to
the compressor.
4. Loosen
screws at feet
of the
compressor.
5. Replace the
compressor
with a new one.
A Series Modular-type Air-cooled (Heat Pump) Chiller
Note: power lines and their
terminals should be numbered to
avoid incorrect rewiring.
123
(1)Remove the insulation of the
compressor;
(2)Loosen screws of power lines
with a screwdriver;
(3)Draw out power lines;
(4)Draw out the electric heater.
(1)Desolder pipes quick to avoid
deformation;
(2)Keep the replaced
compressor complete for
further analysis.
(1)Loosen screws at feet of the
compressor with a adjustable
or box spanner.
(2)Loosened screws should be
put together to avoid loss.
(1)During replacement, care
must be taken to not damage
rubber pads;
(2)Seal the replaced compressor
to prevent moisture entering;
(3)Place a new compressor at
the rubber pads. Steel bushing
is required for rubber pads;
(4)Tighten the steel bushing with
screws.