Gree A Series Service Manual page 128

Modular-type air-cooled (heat pump) chiller
Table of Contents

Advertisement

2. Remove
power lines and
the electric
heater.
3. Disconnect
power lines to
the compressor.
4. Loosen
screws at feet
of the
compressor.
5. Replace the
compressor
with a new one.
A Series Modular-type Air-cooled (Heat Pump) Chiller
Note: power lines and their
terminals should be numbered to
avoid incorrect rewiring.
123
(1)Remove the insulation of the
compressor;
(2)Loosen screws of power lines
with a screwdriver;
(3)Draw out power lines;
(4)Draw out the electric heater.
(1)Desolder pipes quick to avoid
deformation;
(2)Keep the replaced
compressor complete for
further analysis.
(1)Loosen screws at feet of the
compressor with a adjustable
or box spanner.
(2)Loosened screws should be
put together to avoid loss.
(1)During replacement, care
must be taken to not damage
rubber pads;
(2)Seal the replaced compressor
to prevent moisture entering;
(3)Place a new compressor at
the rubber pads. Steel bushing
is required for rubber pads;
(4)Tighten the steel bushing with
screws.