Gree A Series Service Manual page 16

Modular-type air-cooled (heat pump) chiller
Table of Contents

Advertisement

Table 3.6.3
Construction type
Hotel
Large auditorium
Office building
Library, museum
Store
Stadium
Stadium
Cinema
Theater
Hospital
Deluxe restaurant
Note: refer to It is cited from Design and Troubleshooting for Heating and Cooling Air
Conditioners.
(1)Take the lower limit when the total building area is less than 5000m
limit when the total building area is large than 10000 m
(2)The estimated load is directly indicates the required capacity of the air conditioners.
(3)Unless otherwise stated, the area always indicates the total building area no matter if air
conditioning is for local area or not.
3.6.1.2 Calculation of Indoor Load Demand
Indoor load demand = room area (㎡)× per unit load(W/㎡)
Note: our products that will be selected with cooling loads should fit for the on-site situation.
3.6.1.3 Selection of a Terminal Unit
Select a proper terminal unit in accordance with requirements on load noise and installation
space.
3.6.1.4 Selection of a Main Unit
A main unit should be selected based on its theoretically calculated cooling load.
3.6.1.5 Calculation of Heating Load
Calculate the heating loads of the main unit and terminal unit that have been selected, which
is not expected to be recognized until satisfying the requirements.
A Series Modular-type Air-cooled (Heat Pump) Chiller
Estimated Cooling Load per Unit Building Area
Cooling load(W/m
35~45
56~72
42~54
18~32
25~59
35~135
42~68
/
28~45
/
11
2
Cooling load (W/m
56~65 (only service hall)
209~244 (as per the arena
105~122 (as per the total
84~98(only auditorium)
105~128
105~116
2
and take the upper
2
.
2
70~81
/
84~98
35~41
area)
area)
58~81