Connection of power cables

Power cable connection of the I/O modules
The power must be supplied to the FX5-CEX/D, and FX5-C32ET/D.
To supply the power to FX5-CEX/D and FX5-C32ET/D, use two power connectors (upper and lower) on each module for
crossover wiring.
FX5-CEX/DS(-TS) and FX5-C32ET/DS do not have power connectors. Supply the power to them using input connectors
or input terminal blocks.
Input module (extension connector type)
Output module (extension connector type)
FX5-CNV-IF
Input/output module (extension connector type)
Use the following power cables.
Classification
Application
A
Power cable for FX5-CEX/D and FX5-C32ET/D
B
Power crossover cable for FX5-CEX/D and FX5-C32ET/D
• Wiring FX5-CEX/D or FX5-C32ET/D to a subsequent stage
Since the two power connectors on each module of FX5-CEX/D and FX5-C32ET/D are connected in parallel inside the
module, they have no difference and can be either an inlet port or outlet port for supplying the power. Thus, cables can be
connected to either of the connectors.
However, since the lower connector is covered with a resin cover at shipment from the factory, use the upper connector
preferentially. Remove the resin cover only when crossover wiring to a subsequent module is performed.
(FX5-CEX/DS(-TS) and FX5-C32ET/DS do not have power connectors and the power is supplied from using input
connectors or input terminal blocks. Thus, removing the resin cover is not required.)
Precautions
To perform crossover wiring, supply the power from the preceding module to the subsequent module. The power cannot be
supplied from the subsequent module to the preceding module.
The following shows the pin numbers of the power connectors.
FX5-CEX/D, FX5-C32ET/D
1:
(Red)
2:
(Black)
Crossover wiring between input
extension blocks
Resin cover
Since the lower connector is covered with a resin cover at
shipment from the factory, use the upper connector
preferentially. Remove the resin cover only when crossover
wiring to a subsequent extension module is performed.
Red:
Black:
5.5 Connection Methods for CPU Module and Extension Devices
Model
FX2NC-100BPCB
FX2NC-10BPCB1
5 INSTALLATION
5
Length
1 m
0.1 m