Mitsubishi Electric MELSEC iQ-F Series User Manual page 154

Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

Output specifications
There is the simultaneous ON ratio of available PLC inputs or outputs with respect to the ambient temperature. For details,
refer to Page 32 Input/Output Derating Curve.
■Relay output
Item
No. of output points
Connection type
Output type
External power supply
Output circuit insulation
Indication of output operation
Max. load
Open circuit leakage current
Min. load
Response time
Output circuit configuration
*1 When two common terminals are connected outside the I/O module, resistance load is 8 A or less.
APPX
152
Appendix 3 I/O Module
Specifications
FX5-8EYR/ES
8 points
FX5-16EYR/ES
16 points
FX5-16ER/ES
8 points
FX5-32ER/ES
16 points
FX5-C16EYR/D-TS
16 points
FX5-8EYR/ES
Screw terminal block (M3 screws)
FX5-16EYR/ES
FX5-16ER/ES
FX5-32ER/ES
FX5-C16EYR/D-TS
Spring clamp terminal block
Relay
30 V DC or less
240 V AC or less
(250 V AC or less when the module does not comply with CE UL, cUL standards)
Mechanical insulation
LED is lit when output is on
FX5-8EYR/ES
2 A/point
FX5-16EYR/ES
The total load current of resistance loads per common terminal should be the following value.
FX5-16ER/ES
• 4 output points/common terminal: 8 A or less
FX5-32ER/ES
• 8 output points/common terminal: 8 A or less
FX5-C16EYR/D-TS
2 A/point
The total load current of resistance loads per common terminal should be the following value.
• 8 output points/common terminal: 4 A or less
5 V DC, 2 mA (reference values)
OFF→ON
Approx. 10 ms
ON→OFF
Approx. 10 ms
FX5-8EYR/ES
Load
FX5-16EYR/ES
FX5-16ER/ES
FX5-32ER/ES
Fuse
Fuse
FX5-C16EYR/D-TS
Load
Fuse
Fuse
Y
DC power
supply
COM0
Y
AC power
supply
COM1
Y
DC power
supply
COM0
COM0
Y
AC power
supply
COM1
COM1
*1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq fx5uj

Table of Contents