Clearances

The clearances, measured from the edge of the glass, are minimum clearances unless otherwise
stated.
While the unit is operating
The fire must not be installed where curtains
or other combustible materials could come
into contact with the unit. The 400 mm side
clearance includes side walls.
Floor protection
Heat from this fire may affect the appearance
of some materials used for flooring, such
as carpet, vinyl, cork or timber. This may be
amplified if the air contains cooking vapours or
cigarette smoke. To avoid this occurring, it is
recommended that a mat be placed in front of
the fire, extending at least 750 mm in front.
Mantels and surrounds
Mantels and surrounds, made of combustible
materials such as wood, are allowed providing
they are outside the minimum clearances
shown.
Hearths
A hearth is not necessary but can be used for
decorative purposes or protection of sensitive
flooring. A hearth must not obscure the front
face of the fire or obstruct the fire in any way
(including the frame around the fire).
TV installation above the fire
The Arriva has a fan that distributes warm air
from the bottom of the unit out into the room.
As warm air is dispersed outwards, as opposed
to directly upwards, installation of a TV may be
an option.
Generally the bottom of the television should be
at least 400 mm above the fire. Please contact
the television supplier to check clearances.
Some television manufacturers have warranty
conditions that state a TV is not to be installed
above a fireplace.
For further information please contact Rinnai or
refer to the installation guide, which includes a
TV installation diagram.
8 | Arriva 752 operation guide: 12219-C 03-20
400 mm
400 mm
C
A
Mantel needs to be a min. of 400 mm away from
the edge of the inner glass
B
Max. mantel depth at 400 mm (A) is 250 mm
C
Surround needs to be a min. of 400 mm away from
the edge of the glass
For every 50 mm of added mantel depth, there must be
an additional 100 mm of clearance from the edge of the
glass. For example:
Mantel depth
A: Clearance required
300 mm
500 mm
350 mm
600 mm
400 mm
700 mm
400 mm
1000 mm
B
A