Chapter 2 Installation and Wiring
Read the following procedures prior to connecting inputs to the terminals.
WARNING: Ensure the power is off before connecting signal inputs to the unit.
The plug in screw terminal connectors are of the clamping screw variety, putting even pressure on the signal
wire. It is therefore not necessary to terminate the wires with lugs, however you may do so if you wish. The
maximum gauge wire that can be accommodated is 14 AWG or 2.5 mm². You will need a small screwdriver and
a pair of wire cutters and strippers. The use of shielded twisted lead wire is recommended to minimize electro-
magnetically induced noise.
WARNING: All unused inputs must have all contacts commoned togther.
CAUTION: Never run signal and power or control wiring together in the same conduit. This is to
prevent possible recording error due to induced signals between lines. Route signal
wires away from power wires at the rear panel.
NOTE: Ground cable shields at one end only to eliminate the possibility of interference due to
ground loop currents. When grounded transducers are used, the shield should be grounded
at the sensor end only.

2.3.3.1 Thermocouple Inputs

Thermocouple input connections are made as shown in Figure 2-7 T/Cs. Note that a link must be installed
between the "-" terminal and "C" terminal.

2.3.3.2 Resistance Temperature Detector (RTD) Inputs

Two, three or four wire RTDs may be used for connection with cable compensation of ±50 ohms. Refer to
Figure 2-7 RTDs and manufacturing specifications.

2.3.3.3 Linear Inputs

Current inputs: 4-20 milliamps, 0-20 milliamps and 10-50 milliamps, using an external 50 ohm shunt.
Voltage inputs: ±150 millivolts, ±1.25 volts, ±2.5 volts, ±12.5 volts, ±25 volts and normally open/closed
contact inputs. Note that a link must be installed between the "-" terminal and "C" terminal. Refer to Figure
2-7 Volts or mA for details.
Figure 2-7 Thermocouple, RTD and Linear Inputs Wiring Detail