Recommended Accessories; Troubleshooting - Veris Industries E34 Series Installation Manual

Multi-circuit meters
Table of Contents

Advertisement

E34 Series Installation Guide
Recommended
Accessories

Troubleshooting

Z207251-0C
Page 41 of 42
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Part ID
AE001
E3x MCB Cover
CBL008
Flat ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)
CBL016
Flat ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)
CBL017
Flat ribbon cable, 50 x 28 AWG, 5 ft. (1.5 m)
CBL018
Flat ribbon cable, 50 x 28 AWG, 6 ft. (1.8 m)
CBL019
Flat ribbon cable, 50 x 28 AWG, 8 ft. (2.4 m)
CBL020
Flat ribbon cable, 50 x 28 AWG, 10 ft. (3.0 m)
CBL021
Flat ribbon cable, 50 x 28 AWG, 20 ft. (6.1 m)
CBL022
Round ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)
CBL023
Round ribbon cable, 50 x 28 AWG, 10 ft. (3 m)
CBL024
Round ribbon cable, 50 x 28 AWG, 20 ft. (6 m)
CBL025
Flat ribbon cable, 50 x 28 AWG, 2 m
CBL026
Flat ribbon cable, 50 x 28 AWG, 4 m
CBL027
Flat ribbon cable, 50 x 28 AWG, 6 m
CBL031
Round ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)
CBL032
Round ribbon cable, 50 x 28 AWG, 2.5 ft. (0.76 m)
Problem
Product is not communicating over
Modbus daisy chain
RX LED is solid (E34A models)
The main board has a slow flashing
amber light (E34A models)
The main board has a flashing green
light (E34A models)
The main board has a flashing or solid
red light (E34A models)
Power factor reading is not as expected
Current is reading zero, even when
small currents are still flowing through
circuit
Non-zero current or power readings
are showing on one or more unused
channels.
©2020 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Description
• Check the unit Modbus address to ensure that each device on the daisy chain has a unique
address.
• Check Parity.
• Check the communications wiring.
• Check that the daisy chain is properly terminated.
• Check for reversed polarity on Modbus comms.
• Check for sufficient biasing on the Modbus bus. Modbus physical specification calls for 450-650
Ω biasing. This is usually provided by the master.
• One or more channels is clipping. This can be caused by a signal greater than the split-core size
or 277 V L-N, or by a signal with high THD near the gain stage switching points (1.5 A and 10 A).
• Everything is wired properly and the main board has power.
• Light may be red briefly while device powers up.
• If light is red for more the 60 sec. device has encountered a diagnostic event. Contact technical
support.
• The light will flash red if incompatible CT strips or adapter boards are detected
• Verify voltage taps are connected in appropriate phase rotation.
• Verify phase rotation of breakers (firmware rev. 1.012 or higher allows for custom rotation if
needed).
• The product cuts off measurements if the current on any input is less than 0.1% of the full range
current setting used for any CT, and will set the reporting register to 0 mA for currents near or
below this range.
The CT range setting of any channel that does not have a CT actually connected should be set to
zero. Channels without CTs connected will pick up noise that can cause non-zero readings if the
range is not zero. When CTs are properly connected, the impedance of the CT itself will absorb
spurious noise at the proper range setting.
Solution